Boiler Feed Pump Calculator

This boiler feed pump calculator sizes a feedwater pump from steaming rate or flow, drum and deaerator pressure, static head and friction — total head, hydraulic, shaft and motor power.

Boiler Feed Pump Calculator inputs

Extra capacity over the steaming rate for blowdown, attemperation and control (often 10–25%).

Pressure the pump must deliver into: drum or steam outlet pressure plus any margin for safety-valve setting.

Pressure on the suction side (deaerator or feed tank). Use 0 for an open, vented tank.

Negative when the drum level sits below the deaerator level.

Piping, valves, feedwater control valve, economizer and heaters, as head.

Result

Enter your values to see the result.

  • Formula v1.0, unit-tested
  • Examples generated by the calculator
  • Updated
  • How we calculate
On this page

Formula

TDH = (P_drum − P_DA) ÷ (ρ·g) + Z + H_f; hydraulic power = ρ·g·Q·TDH; shaft power = hydraulic ÷ η_pump; motor input = shaft ÷ η_motor; Q = steam rate × (1 + margin) ÷ ρ

P_drum, P_DA
boiler drum (discharge target) and deaerator (suction) gauge pressures, in Pa
ρ
feedwater density in kg/m³, from temperature (saturated water, NIST) or entered directly
g
standard gravity, 9.80665 m/s²
Z
static head, drum water level minus deaerator water level, in m (negative if the drum is lower)
H_f
total friction loss of suction and discharge piping, valves, economizer and heaters, as head in m
Q
feedwater volume flow in m³/s
η_pump, η_motor
pump and motor efficiencies as decimals

A boiler feed pump takes water from the deaerator or feed tank, at low pressure, and pushes it into a boiler drum that may be at hundreds of psi. A boiler feed pump calculation answers two questions: how much head the pump must develop, and how much power that takes at the shaft and at the motor terminals. The calculator does both with the standard pump equations and shows each step, in US or metric units.

How to use the calculator

  1. Flow. Choose the boiler steaming rate (lb/h, klb/h, kg/h, t/h or boiler horsepower) plus a flow margin, or enter the feedwater flow directly in gpm, m³/h, L/s or L/min.
  2. Pressures. Enter the boiler drum pressure the pump must feed into and the deaerator (suction) pressure, both as gauge pressures in psi, bar or kPa.
  3. Static head. The height of the drum water level above the deaerator water level. It is often negative, because deaerators are mounted high to give the pump suction head.
  4. Friction losses. The total for suction and discharge, including the feed control valve, economizer and heaters, in ft or m.
  5. Water. Pick the feedwater temperature (the density is looked up) or type a density.
  6. Efficiencies. Pump efficiency from the curve at the duty point, and motor efficiency from the nameplate.

The result is the shaft (brake) power, with total dynamic head, motor input, hydraulic power, flow, density, pump differential pressure and wire-to-water efficiency beneath it.

Boiler feed pump head calculation by hand

Take a 400 boiler horsepower firetube boiler at 150 psig, a deaerator at 5 psig, feedwater at 220 °F, 20 ft of static lift, 35 ft of friction losses, a 60% efficient pump and a 92% efficient motor.

Flow (capacity): 400 BHP × 34.5 lb/h = 13,800 lb/h of steam. With a 15% margin, the pump must deliver 15,870 lb/h. Water at 220 °F has a density of about 955.1 kg/m³ (59.62 lb/ft³, or 7.97 lb/gal), so the flow is 15,870 ÷ 7.97 ÷ 60 ≈ 33.2 gpm.

Head: the pressure difference is 150 − 5 = 145 psi. At this density one psi is 144 ÷ 59.62 = 2.415 ft of water, so the pressure head is about 350.2 ft. Adding the static and friction head:

TDH = 350.2 + 20 + 35 = 405.2 ft (123.5 m)

Power: water horsepower = gpm × ft × SG ÷ 3,960 = 33.2 × 405.2 × 0.955 ÷ 3,960 ≈ 3.2 hp (2.42 kW). Dividing by the pump efficiency gives 2.42 ÷ 0.60 = 4.04 kW, or 5.4 hp at the shaft. Dividing again by the motor efficiency gives 4.04 ÷ 0.92 = 4.39 kW of electrical input.

The metric route gives the same answer: pressure head = ΔP ÷ (ρ·g), and hydraulic power = ρ·g·Q·H in watts.

Head per psi at feedwater temperatures

The familiar “2.31 ft per psi” is for cold water. Deaerated feedwater is hot and lighter, so each psi is worth more feet of head:

Water temperature Density Head per psi
60 °F (15.6 °C) 998.87 kg/m³ (62.36 lb/ft³) 2.309 ft
140 °F (60 °C) 983.20 kg/m³ (61.38 lb/ft³) 2.346 ft
212 °F (100 °C) 958.35 kg/m³ (59.83 lb/ft³) 2.407 ft
250 °F (121.1 °C) 942.19 kg/m³ (58.82 lb/ft³) 2.448 ft
300 °F (148.9 °C) 918.02 kg/m³ (57.31 lb/ft³) 2.513 ft
350 °F (176.7 °C) 890.48 kg/m³ (55.59 lb/ft³) 2.590 ft

Densities are saturated liquid water from the NIST Chemistry WebBook (IAPWS-95). In a boiler feed pump calculation, using 2.31 for 300 °F water would understate the pressure head by about 8%.

Boiler feed pump sizing calculation in practice

  • Capacity margin. Feed pumps are sized above the maximum steaming rate to cover continuous blowdown, spray attemperation and control-valve authority. The margin varies by plant and by code; use your design basis.
  • Intermittent vs continuous feed. On/off level control on small boilers needs a pump that can refill faster than the boiler evaporates, so the margin is larger than for modulating feed valves.
  • Pressure margin. Many specifications size discharge pressure above the safety-valve set point, not just the operating pressure, so the pump can still feed while the valves lift.
  • NPSH. Hot, saturated water in the deaerator flashes easily. The static height of the deaerator above the pump provides the NPSH; check it against the pump’s NPSH required separately.
  • Running cost. Multiply the motor input by operating hours to get energy use, then use the kWh calculator or the electricity cost calculator to price it.

Common mistakes

  • Mixing absolute and gauge pressure. Use gauge on both sides, or absolute on both; the difference is what counts.
  • Cold-water head factor. Using 2.31 ft/psi for 230 °F feedwater undersizes the head.
  • Forgetting the feed valve. The control valve’s pressure drop at full flow is often one of the largest friction items.
  • Applying the margin twice. If the flow already includes blowdown, set the margin to cover only what is left.
  • Confusing brake horsepower and motor input. Size the motor on shaft power with a service margin; pay the utility for motor input.

Glossary

  • TDH (total dynamic head): total energy per unit weight the pump adds, expressed as a height of liquid.
  • Deaerator: heated tank that strips oxygen from feedwater and serves as the pump’s suction source.
  • Boiler horsepower: 34.5 lb/h of water evaporated from and at 212 °F.
  • Wire-to-water efficiency: pump efficiency × motor efficiency; the share of electrical input that reaches the water.

To work out a fluid’s density from mass and volume, use the density calculator.

Worked examples

A 50,000 lb/h industrial boiler (US units)

50,000 lb/h of steam plus 10% margin, 600 psig drum, 5 psig deaerator, 30 ft static lift, 60 ft friction, 227 °F water, 70% pump, 94% motor.

Inputs: Flow basis = Boiler steaming rate × margin; Boiler steaming rate or rating = 50000; Steaming rate unit = Pounds per hour; Flow margin = 10 %; Boiler drum pressure (gauge) = 600; Boiler drum pressure (gauge) unit = Pounds per square inch; Deaerator pressure (gauge) = 5; Deaerator pressure (gauge) unit = Pounds per square inch; Static head (drum water level − deaerator water level) = 30; Static head (drum water level − deaerator water level) unit = Feet; Friction losses (suction + discharge) = 60; Friction losses (suction + discharge) unit = Feet; Water property = Feedwater temperature; Feedwater temperature = 227; Temperature unit = Fahrenheit (°F); Pump efficiency = 70 %; Motor efficiency = 94 %

Feedwater mass flow = 6.2999 kg/s × (1 + 10%) = 6.9299 kg/s Q = 6.9299 kg/s ÷ 952.18 kg/m³ = 0.007278 m³/s (115.4 gpm) Pressure head = (4,136,854 − 34,474) Pa ÷ (952.18 × 9.80665) = 439.33 m TDH = 439.33 + 9.14 + 18.29 = 466.77 m (1,531.4 ft) Hydraulic power = ρgQH = 952.18 × 9.80665 × 0.007278 × 466.77 = 31.72 kW US check: gpm × ft × SG ÷ 3,960 = 115.4 × 1,531.4 × 0.952 ÷ 3,960 = 42.5 hp Shaft power = 31.72 kW ÷ 0.7 = 45.32 kW (60.8 hp) Motor input = 45.32 kW ÷ 0.94 = 48.21 kW (64.6 hp)

Answer: Boiler feed pump: 115.4 gpm (26.2 m³/h) against 1,531.4 ft (466.8 m) TDH needs 60.8 hp (45.32 kW) at the shaft and 48.21 kW motor input.

A known feedwater flow in metric units

30 m³/h into a 40 bar(g) drum from a 0.3 bar(g) deaerator, 10 m static, 25 m friction, 950 kg/m³, 65% pump, 93% motor.

Inputs: Flow basis = Feedwater flow (direct); Feedwater flow = 30; Flow unit = Cubic meters per hour; Boiler drum pressure (gauge) = 40; Boiler drum pressure (gauge) unit = Bar; Deaerator pressure (gauge) = 0.3; Deaerator pressure (gauge) unit = Bar; Static head (drum water level − deaerator water level) = 10; Static head (drum water level − deaerator water level) unit = Meters; Friction losses (suction + discharge) = 25; Friction losses (suction + discharge) unit = Meters; Water property = Density (enter directly); Water density = 950; Water density unit = Kilograms per cubic meter; Pump efficiency = 65 %; Motor efficiency = 93 %

Q = 0.008333 m³/s (132.1 gpm) Pressure head = (4,000,000 − 30,000) Pa ÷ (950 × 9.80665) = 426.13 m TDH = 426.13 + 10 + 25 = 461.13 m (1,512.9 ft) Hydraulic power = ρgQH = 950 × 9.80665 × 0.008333 × 461.13 = 35.8 kW US check: gpm × ft × SG ÷ 3,960 = 132.1 × 1,512.9 × 0.95 ÷ 3,960 = 48 hp Shaft power = 35.8 kW ÷ 0.65 = 55.08 kW (73.9 hp) Motor input = 55.08 kW ÷ 0.93 = 59.22 kW (79.4 hp)

Answer: Boiler feed pump: 132.1 gpm (30 m³/h) against 1,512.9 ft (461.1 m) TDH needs 73.9 hp (55.08 kW) at the shaft and 59.22 kW motor input.

Edge case: drum level below the deaerator

A 3 t/h package boiler with 20% margin, 10 bar(g) drum, elevated deaerator (−2 m static), 105 °C water, 55% pump, 90% motor.

Inputs: Flow basis = Boiler steaming rate × margin; Boiler steaming rate or rating = 3; Steaming rate unit = Metric tons per hour; Flow margin = 20 %; Boiler drum pressure (gauge) = 10; Boiler drum pressure (gauge) unit = Bar; Deaerator pressure (gauge) = 0.2; Deaerator pressure (gauge) unit = Bar; Static head (drum water level − deaerator water level) = -2; Static head (drum water level − deaerator water level) unit = Meters; Friction losses (suction + discharge) = 8; Friction losses (suction + discharge) unit = Meters; Water property = Feedwater temperature; Feedwater temperature = 105; Temperature unit = Celsius (°C); Pump efficiency = 55 %; Motor efficiency = 90 %

Feedwater mass flow = 0.8333 kg/s × (1 + 20%) = 1 kg/s Q = 1 kg/s ÷ 954.65 kg/m³ = 0.001048 m³/s (16.6 gpm) Pressure head = (1,000,000 − 20,000) Pa ÷ (954.65 × 9.80665) = 104.68 m TDH = 104.68 + −2 + 8 = 110.68 m (363.1 ft) Hydraulic power = ρgQH = 954.65 × 9.80665 × 0.001048 × 110.68 = 1.09 kW US check: gpm × ft × SG ÷ 3,960 = 16.6 × 363.1 × 0.955 ÷ 3,960 = 1.5 hp Shaft power = 1.09 kW ÷ 0.55 = 1.97 kW (2.6 hp) Motor input = 1.97 kW ÷ 0.9 = 2.19 kW (2.9 hp)

Answer: Boiler feed pump: 16.6 gpm (3.77 m³/h) against 363.1 ft (110.7 m) TDH needs 2.6 hp (1.97 kW) at the shaft and 2.19 kW motor input.

Assumptions and limitations

  • Standard pump power equations (Engineering ToolBox, DOE/Hydraulic Institute pumping sourcebook). Results are for preliminary sizing; final selection uses the manufacturer's pump curve at the rated point.
  • Feedwater density comes from saturated-liquid water values (IAPWS-95 via the NIST Chemistry WebBook) every 10 °C from 0 to 250 °C, interpolated linearly. Pressure has a negligible effect on liquid density at this precision.
  • Velocity head and the difference between suction and discharge pipe sizes are ignored, which is normal for feed pumps where pressure head dominates.
  • Friction losses are your input: include suction and discharge piping, the feedwater control valve, check valves, economizer and any feedwater heaters.
  • One boiler horsepower is taken as 34.5 lb of water evaporated per hour from and at 212 °F. The flow margin covers blowdown, attemperation spray and control; it is applied to mass flow before converting to volume.
  • NPSH, minimum-flow recirculation, motor service factor and code requirements (for example ASME boiler code rules on feed capacity and pressure) are not checked.

Frequently asked questions

How do you calculate boiler feed pump head?

Convert the pressure difference between the boiler drum and the deaerator into head with ΔP ÷ (ρ·g), or psi × 2.31 ÷ SG in US units, then add the static height from deaerator level to drum level and the friction losses. The total is the total dynamic head (TDH).

How do you calculate boiler feed pump capacity?

Start from the boiler's maximum steaming rate, add a margin for blowdown and control (often 10–25%), and convert mass to volume with the feedwater density. In US practice, 1 boiler horsepower needs about 0.069 gpm of feedwater before margin.

What pressure should a boiler feed pump deliver?

Enough to overcome the drum pressure plus the static lift and all friction losses on the discharge side, including the feed control valve. Many designs add margin above the safety-valve setting; check the boiler code and manufacturer requirements.

What is the difference between hydraulic, shaft and motor power?

Hydraulic (water) power is the energy actually given to the water, ρ·g·Q·H. Shaft or brake power is what the pump needs at its coupling, hydraulic power divided by pump efficiency. Motor input is the electrical power drawn, shaft power divided by motor efficiency.

Why does feedwater temperature matter?

Hot water is less dense, so the same pressure difference needs more feet of head. At 300 °F one psi equals about 2.51 ft of water, compared with about 2.31 ft at 60 °F. Temperature also sets the NPSH margin, which this calculator does not check.

What efficiency should I use for a boiler feed pump?

Use the efficiency from the pump curve at your duty point. Small multistage feed pumps can be well below 60%, while large ones exceed 80%. Premium-efficiency motors are typically 92–96% at full load.

Sources

  1. Pumps - Power Calculator — The Engineering ToolBox. Checked October 10, 2026.
  2. Improving Pumping System Performance: A Sourcebook for Industry (2nd ed.) — U.S. Department of Energy and Hydraulic Institute. Checked October 10, 2026.
  3. Thermophysical Properties of Fluid Systems (water, saturation properties) — NIST Chemistry WebBook. Checked October 10, 2026.
  4. Proper sizing of Boiler Feedwater Systems — McKenzie Corporation. Checked October 10, 2026.